Curtain Wall Fire Resistance

Perimeter fire barrier between curtain wall and floor slab, EN 1364-4 / ASTM E2307 testing and results.

Curtain wall fire resistance

Aluminium curtain walls are normally used for areas of the building envelope that are not required to be fire resisting. However they still require appropriate detailing to limit the spread of fire and smoke. Where an external wall, such as a curtain wall, abuts a fire-resistant compartment floor, it is necessary to provide fire stopping between the external wall and the compartment floor to restrict fire and smoke spread through the junction.

The fire rating of the floor should be extended through the perimeter seal to the curtain wall. The perimeter fire barrier system provides structural protection. This can help to keep the wall and window system intact for a longer period of time. The fire resistance performance of the perimeter fire barrier and its ability to maintain a seal to prevent fire from spreading among an exterior wall assembly and floor assembly can be evaluated according to ASTM E2307 or EN1364-4. Through this test, both the performance (deflection and fire resistance) of the spandrel area in the curtain wall can be seen, as well as the performance of the perimeter barrier seal system (passage of smoke/hot gases/flames, temperature rise). This fire test simulates an indoor fire located near the curtain wall spandrel area, below the perimeter barrier seal. DOWSIL™ Sealants can be implemented in these types of perimeter barrier systems as a smoke seal. Please contact your local Dow Technical Specialist to learn more about the use of DOWSIL™ Silicones in perimeter barrier systems. DOWSIL™ Firestop 700 Sealant and DOWSIL™ Smoke Seal 800SL have been tested successfully in perimeter barrier systems. The achieved performance is valid for the used façade system. More details on the perimeter barrier seal parameters can be provided on request. Please consult with your local Technical Specialist.

Figure 16.1 and 16.2: Curtain wall and fire-resistant floor and walls with indication of the use of fire resistant silicone for linear joints in compartments and on top of the mineral wool in the perimeter barrier system between floor and curtain wall. 1) Curtain wall, 2) Fire rated silicone, 3) Mineral wool, 4) Concrete floor slab, 5) Steel sheet
Figure 16.1 and 16.2: Curtain wall and fire-resistant floor and walls with indication of the use of fire resistant silicone for linear joints in compartments and on top of the mineral wool in the perimeter barrier system between floor and curtain wall. 1) Curtain wall, 2) Fire rated silicone, 3) Mineral wool, 4) Concrete floor slab, 5) Steel sheet
Figure 16.1
Figure 16.1
ProductGap Width Floor to Curtain WallSteel sheet thicknessStandardIntegrityInsulationDrawingReport
700125 mm2 mmEN1364-412012016.1XK041-2B
Figure 16.2
Figure 16.2
ProductPremier Gap WidthStandardIntegrityInsulationDrawingReport
800125 mmEN1364-412012016.2XK041-2B