TECHNICAL MANUAL 10 / 16 · Original pp. 20–21

Linear Joints in Floors – Test Results

Tested floor joint designs, shear movement and results for DOWSIL™ Smoke Seal 800SL, 790 and 3-6548 Foam.

Linear joints in floors

The table below combines the joint design (original manual page 20) with the corresponding test result (page 21), row by row. Shear movement is given as a percentage of the joint width. Integrity (E) and insulation (I) are in minutes.

32 test results · scroll the table horizontally and vertically.
MaterialDrawingBite widthThickness/ depthSingle-doubleShear movementBacking typeBacking thicknessDensity/ compressionWall materialWall thicknessTested standardIntegrity (E)Insulation (I)Report
800SLL462NFS0MW100mm45kg/m3/10%Aerated CC150mmEN1366-424024019921A
800SLL4502NFS0MW100mm45kg/m3/10%Aerated CC150mmEN1366-424024019921A
800SLL45010NFS0MW100mm45kg/m3/10%Aerated CC150mmEN1366-424024019921A
800SLL410010NFS0MW100mm45kg/m3/10%Aerated CC150mmEN1366-424012019921A
800SLL415010NFS0MW100mm45kg/m3/10%Aerated CC150mmEN1366-42409019921A
800SLL462NFS10%MW100mm45kg/m3/10%Aerated CC150mmEN1366-424024019921A
800SLL4502NFS10%MW100mm45kg/m3/10%Aerated CC150mmEN1366-424018019921A
800SLL466NFS25%MW100mm45kg/m3/10%Aerated CC150mmEN1366-418012019921A
800SLL4206NFS25%MW100mm45kg/m3/10%Aerated CC150mmEN1366-424024019921A
800SLL45010NFS25%MW100mm45kg/m3/10%Aerated CC150mmEN1366-424024019921A
800SLL410010NFS25%MW100mm45kg/m3/10%Aerated CC150mmEN1366-418012019921A
800SLL415010NFS25%MW100mm45kg/m3/10%Aerated CC150mmEN1366-424012019921A
800SLL3106NFS0PE10mm35kg/m3Aerated CC150mmEN1366-424024019921A
800SLL3206NFS0PE20mm35kg/m3Aerated CC150mmEN1366-4601519921A
800SLL3306NFS0PE30mm35kg/m3Aerated CC150mmEN1366-4601519921A
800SLL3106NFS25%PE10mm35kg/m3Aerated CC150mmEN1366-424024019921A
800SLL3206NFS25%PE20mm35kg/m3Aerated CC150mmEN1366-4601519921A
800SLL3306NFS25%PE30mm35kg/m3Aerated CC150mmEN1366-460NA19921A
800SLL31006NFS0MW120mm110kg/m3/10%Aerated CC200mmEN1366-4120120P110312-1006
800SLL3506NFSNAMW100mm100kg/m3/33%Aerated CC115mmUL20792-3hourFTXHBN FF S0040
800SLL31506NFSNAMW100mm100kg/m3/33%Aerated CC115mmUL20792-3hourFTXHBN FF S 1043
790L31015FSNAPE10mm35kg/m3Aerated CC120mmBS476/20120120FSP0040
790L31515FSNAPE15mm35kg/m3Aerated CC120mmBS476/20120120FSP0040
790L11015FS+NFSNAPE10mm35kg/m3Aerated CC120mmBS476/20180180FSP0095
790L11515FS+NFSNAPE15mm35kg/m3Aerated CC120mmBS476/20180180FSP0095
790L12015FS+NFSNAPE20mm35kg/m3Aerated CC120mmBS476/20180180FSP0095
790L31015FSNAPE10mm35kg/m3Aerated CC120mmBS476/20240240FSP0040
790L31515FSNAPE15mm35kg/m3Aerated CC120mmBS476/20240240FSP0040
790L32510NFSNAPE+CF10mm+60mm35+100kg/m3Aerated CC170mmBS476/20240240FSP0246
790L12525FS+NFSNAPE25mm35kg/m3Aerated CC170mmBS476/20240240FSP0246
3-6548L45010NFS25%MW100mm45kg/m3/10%Aerated CC150mmEN1366-412012019921A
3-6548L410010NFS25%MW100mm45kg/m3/10%Aerated CC150mmEN1366-512012019921A
These are typical properties, not to be construed as specifications.
Fire-rated sealant inquiries

For supply, quotations and technical questions on DOWSIL™ fire rated sealants, contact us. Source: Dow technical manual (Form No. 62-2233-01-0325 S2D, © 2025 The Dow Chemical Company).

sales@kconstrade.comWhatsApp