TECHNICAL MANUAL 8 / 16 · Original pp. 14

Linear Joints – Seal Types L1–L4

The four tested designs (L1–L4) used for all linear joints in walls and floors, with legend.

Linear joints test results

The following pages depict the linear joint designs that have been tested to:

  • European standard EN1366-4
  • British Standard BS476-20
  • UL 2079

All linear joints follow one of the four designs below for wall and floors. In walls, the joints can be both horizontal or vertical.

Seal type L1 is a symmetric seal joint supported on both sides of the construction by a backer rod and finished flush with the surface of the supporting construction, wall or floor
Seal type L1 is a symmetric seal joint supported on both sides of the construction by a backer rod and finished flush with the surface of the supporting construction, wall or floor
Seal type L2 is a symmetric seal joint supported on both sides of the construction by stonewool and finished flush with the surface of the supporting construction, wall or floor
Seal type L2 is a symmetric seal joint supported on both sides of the construction by stonewool and finished flush with the surface of the supporting construction, wall or floor
Seal type L3: single seal joint on a backer rod, finished flush with the surface of the supporting construction, wall or floor. The joint can be on the non-exposed side (non fire side NFS) as illustrated, or on the exposed fire side (FS).
Seal type L3: single seal joint on a backer rod, finished flush with the surface of the supporting construction, wall or floor. The joint can be on the non-exposed side (non fire side NFS) as illustrated, or on the exposed fire side (FS).
Seal type L4: single seal joint on a stonewool backing, finished flush with the surface of the supporting construction, wall or floor. The joint can be on the non-exposed side (non fire side NFS) as illustrated, or on the exposed fire side (FS).
Seal type L4: single seal joint on a stonewool backing, finished flush with the surface of the supporting construction, wall or floor. The joint can be on the non-exposed side (non fire side NFS) as illustrated, or on the exposed fire side (FS).
Legend: 1: sealant depth, 2: sealant width, 3: backfilling depth/diameter, 4: supporting construction depth, 5: fire side