Classification of DOWSIL™ Sealants
The table below summarizes the reaction to fire tests and the obtained classifications according to EN13501-1 for DOWSIL™ Fire Rated Sealants. As explained, sealants and seals are typically exempted from the A1 or A2 requirement. However, these materials can be used in assemblies which require the knowledge of the calorific power following the EN ISO 1716. Therefore, the excellent calorific power (MJ/kg) of the DOWSIL™ Fire Rated Sealant Range as well as typical high performance building sealants has been assessed. Please contact your local Dow Technical Specialist to obtain these values.
| Product | EN ISO 1716 | EN ISO 13823 | EN ISO 11925 | ASTM E84 | Classification |
|---|---|---|---|---|---|
| DOWSIL™ FIRESTOP 700 Sealant | X | X | X | — | Class: B,s2,d0 |
| DOWSIL™ 813 FR Fire Retardant Silicone | X | X | X | — | Class: B,s2,d0 |
| DOWSIL™ 790 Building Sealant | — | — | X | E | Class: E |
| DOWSIL™ Smoke Seal 800SL | X | — | X | — | Class: E |
| DOWSIL™ 3-6548 Silicone RTV Foam | X | — | X | — | Class: E |
For the EN13823 sealant material tests, the full corner surface should be covered homogeneously with sealant. To ensure the test results can be used for a range of thicknesses of the sealant, both a minimum and maximum thickness were tested. For the small flame test EN11925, a linear joint was tested.
More information concerning reaction to fire behavior can be obtained from your local Dow Technical Specialist.

More technical resources
For supply, quotations and technical questions on DOWSIL™ fire rated sealants, contact us. Source: Dow technical manual (Form No. 62-2233-01-0325 S2D, © 2025 The Dow Chemical Company).