SEALANT SELECTION 4 / 9 · 규격 요약

Firestop Standards Compared: ASTM E119, E814/UL 1479, E1966 vs. EN 1366-3/-4

How North American and European fire-resistance tests for penetration seals and linear joints relate, and what E, I, F and T ratings mean.

KEY FACTS

EN 1366-3 (penetration seals) and EN 1366-4 (linear joint seals) are classified under EN 13501-2 as E (integrity) and I (insulation) in minutes. In North America, penetration seals are tested to ASTM E814 / UL 1479 (F and T ratings) and linear joints to ASTM E1966 / UL 2079. ASTM E119 is the general fire test for building construction. The ratings are not interchangeable; use the standard your project or authority requires.

Standards at a glance

Fire-resistance test standards (from the Dow fire-rated manual and general knowledge)
Fire-resistance test standards (from the Dow fire-rated manual and general knowledge)
ApplicationEuropeNorth AmericaRating
Penetration sealsEN 1366-3 / EN 13501-2ASTM E814 · UL 1479E, I (min) / F, T (hours)
Linear jointsEN 1366-4 / EN 13501-2ASTM E1966 · UL 2079E, I (min) / hours
Wall/floor elements in generalEN 1364 / EN 1365 / EN 13501-2ASTM E119Minutes / hours
Curtain wall, perimeter jointEN 1364-4 (curtain walling)ASTM E2307 (perimeter fire barrier)Confirm
Korea: fire-stop structureConfirmConfirmConfirm
EN 1366-3/-4, EN 13501-2, UL 1479, ASTM E814, UL 2079 and ASTM E1966 are cited in the Dow fire-rated manual. EN 1364-4, ASTM E119 and ASTM E2307 are listed from general standard titles. Korean system details: confirm with the authority.

E, I and F, T ratings

  • E (integrity): prevents passage of flames and hot gases; failure includes sustained flaming over 10 s or gap gauge penetration (6 mm / 25 mm gauges).
  • I (insulation): mean unexposed face temperature rise limited to 140 °C, any point 180 °C above initial.
  • F and T ratings (ASTM E814 / UL 1479): F relates to flame passage, T adds the temperature criterion on the unexposed side. Numeric criteria: confirm in the standard.
E and I criteria above are quoted from the Dow manual (see /technical/fire-resistance).

Korean approval system

Korea has its own approval route for fire-stop structures. The applicable test standard, approval body, validity period and how foreign test reports are accepted were not verified here, so they are marked “confirm”. Ask KCT to check the current Dow reports and your project’s requirement.

References

Frequently asked questions

Is ASTM E814 the same as EN 1366-3?

Both test penetration seals, but test method, exposure and rating system differ (F/T vs. E/I), so results are not directly interchangeable.

Which standard covers linear joints?

EN 1366-4 in Europe; UL 2079 and ASTM E1966 in North America (per the Dow manual).

What do E and I mean?

E = integrity (flames and hot gases blocked), I = insulation (unexposed side temperature limited); each expressed in minutes.

Is EN 1366 accepted in Korea?

We could not verify this; acceptance depends on the Korean approval system and the authority. Ask KCT.

Who can support this at KCT?

Korea Construction Trading (KCT) supports DOWSIL product selection and documentation requests: sales@kconstrade.com, +82 10-8939-0284. Final requirements are confirmed with Dow and the authority having jurisdiction.

Source and citation

This page is based on the following document. Values are typical, not specifications; verify with the original and product data sheets before design or purchase.

Dow 제품 기술 데이터시트(TDS)의 대표 특성을 한국건설트레이딩(KCT)이 같은 기준으로 요약·비교 (각 제품 페이지의 TDS PDF 참조). 수치는 시방용이 아님

Suggested citation: “Firestop Standards Compared: ASTM E119, E814/UL 1479, E1966 vs. EN 1366-3/-4”, Korea Construction Trading (KCT) Technical Information, https://kconstrade.com/en/technical/selection/astm-e119-vs-en-1366-firestop

Inquiries · Korea Construction Trading (KCT)

For DOWSIL™ silicone selection, quotations and technical advice, please contact Korea Construction Trading. We do our best to support you technically, from product selection to process-condition review and troubleshooting. Technical support details →

sales@kconstrade.com010-8939-0284WhatsApp